General | Measuring system | 1Ø | |
LCD Screen | ✔ | ||
Language Support | Turkish, English | ||
Password Protection | ✔ | ||
Current Transformer Ratio | 1 – 5.000 | ||
Voltage Transformer Ratio | 1 – 999.9 | ||
Connection Type | L-L/L-N | ||
Number of Measurements in a Period | 512 | ||
LCD/Display Refresh Period | <0.5 sec. | ||
Networks | TT, TN, | ||
Signal Waveforms | |||
Control Operations and Functions | Compensation Modes | Rapidus (Intelligent control mode) | ✔ |
Manual | ✔ | ||
Step Configurations | Manually Assigned | ✔ | |
Predefined | 1-1-1-1, 1-2-2-2, 1-2-4-4 | ||
Power (kVAr) | 0.00-1000 adjustable | ||
Type | 3Ø capacitor, 1Ø capacitor | ||
Power Factor Settings | Target 1 cosØ | 0.8 cap. to 0.8 ind. adjustable | |
Target 2 cosØ | 0.8 cap. to 0.8 ind. adjustable | ||
Control Operations and Functions | Dual cosØ Target | ✔ | |
4 Quadrant operation for generators | ✔ | ||
Time Delays | Step Activation Time | 1-600 sec. adjustable | |
Step Deactivation Time | 1-600 sec. adjustable | ||
Step Discharge Time | 3-1000 sec. adjustable | ||
Energy Measurement | Multi Sub-Tariffs (Peak, Day and Off-Peak) | ||
1Ø Phase Energy Meters | |||
3Ø Phase Energy Meters | |||
4 Quadrant Reactive Energy Meters | |||
Current Measurement Input | Measurement Range | 10mA-6A AC | |
Overvoltage Category | 300 V Cat III | ||
Measurement Surge Voltage | |||
Power Consumption | <0.2 VA | ||
Intermittent Overload | 100A for 1 sec. | ||
Sampling Frequency between 45-65 Hz | 25.6 kHz | ||
Voltage Measurement Input | Overvoltage Category | 300 V Cat III | |
Measured Range L-N | 120…510V AC ±10% | ||
Measured Range L-L | 120…510V AC ±10% | ||
Measured Frequency Range | 45-65 Hz | ||
Power Consumption | <0.2 VA | ||
Sampling Frequency between 45-65 Hz | 25.6 kHz | ||
Power Quality Measurements | THD – Voltage in % | ✔ | |
THD – Current in % | ✔ | ||
Measurement Accuracy | According to IEC 61557-12 | Total Active Power | Class 0.5 |
Total Reactive Power | Class 1 | ||
Total Apparent Power | Class 0.5 | ||
Total Active Energy | Class 0.5 | ||
Total Reactive Energy | Class 2 | ||
Frequency | Class 0.1 | ||
Current | Class 0.5 | ||
Neutral Current | Class 0.5 | ||
Voltage | Class 0.2 | ||
Power Factor | Class 0.5 | ||
THDV, THDI | Class 1 | ||
According to IEC 62053-22 | Total Active Energy | Class 0.5S | |
According to IEC 62053-23 | Total Reactive Energy | Class 2 | |
Input and Outputs | Compensation Relay Outputs | Number of outputs | 10 |
Type | NO (SPST) | ||
Max. Switching Current | 2A | ||
Max. Switching Voltage | 250VAC | ||
Max. Switching Power | 1250VA | ||
Mechanical Lifetime | ≥ 10.0000000 operations | ||
Electrical Lifetime Operations (for NO side) | 5×104(5A@250VAC) 1×105(5A@30VDC) | ||
Alarm Relay Outputs | Number of outputs | 2 | |
Type | NO (SPST) | ||
Max. Switching Current | 4A | ||
Max. Switching Voltage | 250 VAC | ||
Max. Switching Power | 1250 VA | ||
Mechanical life time | ≥ 10.0000000 operations | ||
Electrical life time operations (for NO side) | 5×104(5A@250VAC) 1×105(5A@30VDC) | ||
Generator/ Day-Night Input | Number of Inputs | 1 | |
Frequency | 45-65Hz | ||
Input Present or Not | 95-240VAC | ||
Input and Outputs | Digital Outputs | — | |
Analog Outputs | — | ||
Supply | Auxilary Supply Input | — | |
Voltage | La-Lb’den 120…510V AC ±10% | ||
Frequency | 45-65Hz | ||
Supply | Consumption | AC | < 10VA |
DC | — | ||
Mechanical Properties | Weight (g) | ||
Protection Class | Front IP40 / Rear IP20 | ||
Mounting Type | Panel Mount | ||
Packing Unit | 1 | ||
Cable Cross Sections | Voltage, Current, All Relay Outputs, Gen Input | Stranded: | 2.5mm² – 14AWG |
Ambient Conditions | Operating Temperature | -20°C +55°C | |
Storing Temperature | -30°C +80°C | ||
Relative Humidity (no condensation) | Maks. 95% | ||
EMC-EMI | EN 61000-6-1:2011 | ✔ | |
EN 61000-6-3/A1/ AC:2013 | ✔ | ||
Schematics | Network Connections | ✔ | |
Step Output Connections | ✔ | ||
Digital I/O and Alarm Output Connections |
Power Factor Controller
RAPIDUS 1 series is a monophase Reactive Power Control relay. It has 4, 6, 8, 10 and 12-steps options and an optional RS485 port. The built-in temperature sensor measures the panel temperature and the fan output can be controlled by the relay outputs.
Reviews
There are no reviews yet.