Specifications
- Area Classification
- Intrinsically Safe, Explosion Proof, Dust Ignition Proof, Flame Proof, Non-incendive, Type N
- Certifications
- CSA, FM, ATEX, KGS, Peso, CIMFR, NEPSI, TIIS, Ukraine Metrology, Belarus Metrology, Kazakhstan Metrology, IECEx, INMETRO, CUTR
- Communication Protocol
- HART®, 4-20mA Analog
- Data Interface
- Wired
- Diagnostics
- Yes
- Mounting Type
- 249 Series Torque Tube Arm Mounted
- Operating Temperature
- Standard Temperature
- Position Control
- Monitoring
- Power Source
- Loop Powered (2-Wire)ed (2-Wire)
- Process Control
- Level
- Other Configurations
- Contact your local Emerson business partner or sales office to learn about additional specifications or options for this product.
Features
- For quick analog transmitter replacement, the instrument may be configured with default sensor data, zero level offset, differential process SG, and zero/span procedure only.
- Accurate, high-gain analog-to-digital conversion enables measurement of small changes in the process variable. This allows for use in difficult liquid level, interface, or density applications.
- An internal temperature sensor enables consistent performance of the digital level controller, despite ambient temperature changes.
- Mechanical safeguards designed into the digital level controller help to withstand physical abuse often incurred during installation or in transport, without compromising performance.
- Field wiring connections are in a compartment separated from the electronics. This protects the electronics from any moisture brought into the housing by the field wiring.
- Includes self-diagnostics that detect an error that may render the process variable measurement inaccurate.