Specifications
- Area Classification
- Explosion Proof, Intrinsically Safe, Non-incendive, General Purpose, Flame Proof
- Certifications
- CSA, FM, ATEX, IECEx, CUTR, Regional
- Communication Protocol
- 4-20mA Analog
- Data Interface
- Wired
- Diagnostics
- No
- Input Signal
- Electric
- Max Outlet Pressure
- 35 psig
- Mounting Type
- Remote Mount, Actuator Mount
- Operating Temperature
- Standard Temperature
- Position Control
- Modulating Control
- Power Source
- Local
- Supply Media
- Air
- Other Configurations
- Contact your local Emerson business partner or sales office to learn about additional specifications or options for this product.
Features
- The low-mass pilot stage, mechanically damped deflector bar, and rugged construction provide stable performance in vibration.
- Large diameter nozzles, free-flow pilot stage design, and large internal pneumatic supply passages provide excellent tolerance to reducing the effects of contaminant build-up and erosion.
- The electronic feedback control network monitors the pneumatic output signal, detects any input-output deviations and corrects them.
- Major mechanical and electrical components are incorporated into a single field-replaceable master module.
- With Stroke Port, a constant bleed from the pilot stage vents through a hole in the module cover. Covering the hole increases the transducer output to confirm the proper operation of the pilot and booster stages and stroke the actuator.